Engineering
Power Factor Correction Calculator
Calculate current and target kVA, kvar, and line current from fixed active power and two power factors. Quantify idealized correction kvar, apparent-demand reduction, and an entered kVA demand-charge difference.
Decision view
Before-and-after power triangles
| Target power factor | Current apparent power (kVA) | Target apparent power (kVA) | Current reactive power (kvar) | Reactive power at target PF (kvar) | Idealized capacitor correction (kvar) | Current three-phase line current (A) | Target three-phase line current (A) | Apparent-power reduction | Modeled demand-charge difference |
|---|
How to use Power Factor Correction Calculator
- Enter fixed active load power.
- Enter present and target power factors.
- Enter the three-phase line voltage.
- Use the kvar correction as a planning value and interpret tariff savings separately.
Calculator guide
Understanding Power Factor Correction Calculator
Power-factor correction reduces reactive and apparent demand while leaving the active load power unchanged. This calculator compares the present and target power triangles and exposes the idealized capacitor kvar rather than treating the change as an energy-efficiency gain.
Calculation method
How the calculation works
Detailed calculation process
Hold active power constant while shrinking the reactive leg
The defaults correct a 180 kW load from PF 0.72 to PF 0.95 at 400 V.
What each symbol means
Worked substitution with the default inputs
The default correction reduces apparent demand from 250.000 to 189.474 kVA, line current from 360.844 to 273.482 A, and reactive demand by 114.330 kvar.
Before and after
Compare two power triangles on one active-power base
The target case shows exactly which electrical quantities shrink.
Worked situations
Practical examples
- A 180 kW load at PF 0.72 draws 250 kVA.
- Raising PF to 0.95 reduces idealized current by about 87.362 A.
- The idealized correction is 114.330 kvar.
Better inputs
Useful tips
- Do not target unity PF without a system study.
- Check utility billing before assigning savings.
- Select staged equipment for variable loads when appropriate.
Before relying on the result
Limitations and common mistakes
- Harmonics, resonance, switching, detuning, voltage rise, and motor behavior are excluded.
- Actual capacitor-bank sizes use standard steps and engineering margins.
- Energy charges usually do not fall solely from improving PF.
Reference
Key terms
- Correction kvar
- Reactive power supplied locally by correction equipment.
- Power triangle
- Right triangle relating kW, kvar, and kVA.
- Demand charge
- Charge based on a billing-period capacity measurement.
Important note
Calculated from the entered values using the displayed engineering relationship. Confirm design values, load cases, safety factors, standards, and field conditions with a qualified professional.
Frequently asked questions
Does correction reduce active kW?
The idealized calculation holds active load power constant.
Why not always choose PF 1.00?
Overcorrection, resonance, switching, and changing load conditions require engineering review.
Is Qc the installed bank rating?
It is an idealized need; practical selection uses available stages and system studies.
Why can savings be zero?
Utilities that bill only kWh may not reward reduced kVA directly.